Option 2

Maintain Gas Flow and Build a Bypass

Service maintained · ~4,000 customers

Crews build a temporary bypass around the damaged section so customers keep gas service, then cut out and replace the damaged pipe.

Gas service
Stays on
Damaged section isolated
After the bypass is built and the segment is blown down
Permanent repair
Two weeks
Worker hazard
Welding into a mix of gas and air
Also
Continuous, 24-hour excavation; traffic re-routed (Class 3 location)
  1. Step 1 of 7

    Gas leak

    Where things stand

    Gas is still escaping from the damaged main, and the fire department remains on scene.

  2. Step 2 of 7

    Gas leak

    Dig on both sides of the damage

    Crews begin continuous, 24-hour excavation upstream and downstream of the damaged area.

  3. Step 3 of 7

    Gas leak

    Install hot taps on the live line

    Leak-proof taps are installed into the pipeline at either end of the damaged area while gas keeps flowing.

    Worker hazardWelding into a mix of gas and air can lead to sparks and ignition, since the line isn’t shut down. Pressure is reduced as low as possible, workers wear flame-retardant fire suits and self-contained breathing apparatus, and the fire department stands by with hoses charged.
  4. Step 4 of 7

    BypassGas leak

    Build the bypass

    A bypass is constructed between the two taps to divert flow from the damaged segment. Customers keep gas service.

  5. Step 5 of 7

    Bypass

    Blow down the damaged segment

    Gas is blown down to vacate the impacted segment before it is cut out.

  6. Step 6 of 7

    New pipeBypass

    Cut out and replace

    With the bypass providing gas service, repair crews work within normal business hours to cut out the damaged pipe and install a new segment.

  7. Step 7 of 7

    New pipe

    Return to normal flow

    The bypass is disabled and gas flows normally through the new pipe. The permanent repair takes two weeks, and traffic must be re-routed because this is a densely populated Class 3 location.